Filling station operator. Job description of the operator of the gas station

The operator of the gas station during his work is obliged to adhere to clearly defined goals and objectives, as well as to take responsibility. However, he has rights that protect him. labor activity. This employee is subordinate to the administrator of the gas station. The gas station operator himself must manage the work of the tankers and the janitor. The main responsibilities include mastering the techniques of using cash registers at full capacity. You should also familiarize yourself with the operation of control terminals and devices for servicing electronic cards.

Operator knowledge

  1. All standards and regulations that relate to the work of an employee of this position. This applies to orders and orders, which are not only known for a long time, but also come in real time. Knowledge of everything related to the full-fledged operation of the gas station and the entire structure of the gas station is required.
  2. Drafting cash documents according to pre-established forms and with additions, amendments recommended by the company.
  3. Basic rules for the acceptance, collection, re-accounting, storage and delivery of all funds received from customers.
  4. Instructions for the design and completion of all incoming and outgoing documentation.
  5. Limits on the balances that can be stored in the cash container, which are individually set for a particular enterprise or even for its branch.
  6. Features of maintaining a cash book, counting all funds and compiling financial reports.
  7. Features and performance characteristics cash registers, terminals for servicing various electronic cards and control terminals.
  8. Rules recommended for familiarization and impeccable observance by all employees of the enterprise. Usually they relate to the ability to behave with customers, observe safety precautions, prevent a fire hazard, maintain and impeccably carry out the internal routine of the establishment.
  9. Features of job descriptions that are intended for the janitor and tanker.

Goals

  1. As fast and correct service as possible, which not only gives customers positive emotions, but also produced in the shortest possible time. In carrying out all operations, not only accuracy and quality are required, but also accuracy even in small details.
  2. Maintaining the active functioning of gas stations without failures and unforeseen situations, quick settlement of disputes.
  3. Servicing the maximum number of customers, and with high quality and in a short time.
  4. Clarity and precise coordination in the work of all employees of the gas station.

Functional responsibilities

  1. Appear at work only in clean and tidy clothes, constantly maintain a pleasant appearance.
  2. Provide customer service exclusively in accordance with the rules regulated by the charter of the company.
  3. Perform all types of operations for the release of ordered goods, product sets and other elements, as well as accept cash, recalculate them and give change to the client.

Features of cash payments

Stages of making cash payments for a monetary amount or when calculating the number of liters:

  1. The operator-cashier of the gas station accepts funds from the client, having calculated the amount by the number of liters or the final purchase invoice. Be sure to take into account information about the type of fuel, which is being refueled, and the number of the fuel dispenser.
  2. Clearly dictate to the client the amount received from him, along with this, it is necessary to name the exact number of liters, type of fuel and clarify the number of the fuel dispenser.
  3. Connect the supply of fuel for the amount given by the client of the establishment, as well as accurately calculate the number of liters for which the payment was made from the client.
  4. Break the check, entering into it all the information related to the transaction with a particular client.
  5. Name the exact amount of change that the client is entitled to, as well as issue the necessary funds together with the check. It is necessary to issue a paper check and a change coin exactly at the same time. This includes duties gas station operator.

Cash settlement

The procedure for cash settlement, that is, determining the amount up to a full tank.

  1. Get information and accurately remember all the data that was spoken by the client. It is necessary to accurately indicate the type of fuel chosen, the number of the fuel dispenser, and also receive the assigned amount from the client.
  2. Indicate for the client the amount that was accepted from him. The gas station operator also announces the exact number of liters that will be filled into the tank. Together with this information, the type of fuel and its fuel dispenser number are specified.
  3. Fuel must be dispensed in the number of liters that the client paid for.
  4. When the fuel dispenser is stopped, it is necessary to break the check, which is done by specifying the entire necessary information in the settlement cash register.
  5. Clearly indicate the amount that the change includes, and then give the rest of the money to the buyer along with the check. This includes the duties of the gas station operator.

Cashless payments

The procedure for paying through TNK electronic cards.

  1. Ask the client for his electronic card, while accurately remembering the order parameters, which include the type of fuel, the number of liters, as well as the fuel dispenser number.
  2. Insert the card into a special terminal and see the balance of funds on the client's account.
  3. Clearly set for the client the number of liters of fuel that will last until the tank is completely filled, as well as once again specify the type of fuel liquid together with the fuel dispenser number.
  4. Connect the supply of fuel in the amount that the client has named, and also in the mode until the full tank, you should release the goods no more than there is money on the client's card.
  5. When the dispenser is stopped, you should write out a check, punching all the necessary data on the cash register.
  6. The check and the card must be issued to the client at the same time, which will mean the end of the transaction. This includes working as an operator at a gas station.

Cashless payment by coupons

Rules and procedure for conducting a transaction on non-cash payment by coupons.

  1. Take a coupon from the client and remember the information regarding the dispenser number.
  2. Speak for the client the number of the fuel dispenser, the type of fuel, and clarify required amount liters.
  3. Release the goods, that is, give the task to the tankers, and you should fill in as much fuel as stated in the coupon.
  4. Get a check by entering all the necessary information about the purchase into the cash register.
  5. Cut the coupon along a specially designated line, put a stamp on both parts, and then give the half that is intended for the client. This is what a gas station operator should do. Reviews indicate that this work includes many small but important tasks.

Additional Responsibilities

  1. Give money to customers after paying them only if the total amount of ordered fuel exceeds the space in the tank allotted for it.
  2. In every possible way ensure the safety of the exact amount of money in the cash register.
  3. Quickly solve problems associated with the presence of unauthorized persons in the workplace, which is designed specifically for gas station operators.
  4. Always handle money with care and prevent contamination. Leaving inscriptions on banknotes is also excluded. This is provided for by the instruction of the operator of the gas station.

The procedure for transferring money to collectors

  1. Pre-calculate and prepare the exact amount of money that is given to collectors during their scheduled visit to a gas station employee.
  2. Fill in and check the accuracy, relevance of information for three identical statements of a transmissive nature.
  3. Verify the identity of all bank employees. Often this is done by the senior operator of the gas station.
  4. Wait for the cashiers to fill out a receipt for receiving money, and also receive it from these employees, which will allow transferring responsibility for saving material resources to these employees.

The operator of the gas station must be attentive at the workplace, be distinguished by the position of competence, have all necessary knowledge which will allow him to successfully and flawlessly perform his own duties. The labor activity of this employee provides for both financial responsibility and many job responsibilities, so quality work must be ensured without fail. Fulfillment of one's own duties will help the employee to remain in the position of gas station operator for a long time.

Operator petrol station- an official with whom the client directly communicates, that is, enters into commodity-money relations with him, makes claims to him, seeks clarifications, etc. In addition, the professional activity of the operator is associated with the use of technically complex and unsafe equipment, which requires knowledge.

Well, and finally, the influence of the constant proximity of solid amounts of cash (against the background of a salary that is not always satisfactory for the gas station operator) and the abundance of a sought-after product - motor vehicle fuel. All of the above features leave a definite imprint on the list of qualities that a this worker. This is sufficient technical literacy, responsibility, attention, patience, communication skills and the ability to peacefully resolve conflict situations.

Responsibilities of the operator of the gas station, defined by the job description

2.1 The job description of the gas station operator is the main document regulating professional activity an official who receives, issues and records oil products at a gas station in accordance with the requirements, established Rules technical operation of filling stations and other regulatory legal acts regulating their (gas stations) work.

2.2 The operator-cashier at the gas station is obliged to know and strictly comply with the requirements of the following Rules and instructions:

  • Safety Regulations (PTB) and Technical Operation Rules (PTE) for electrical installations.
  • Rules safe operation filling equipment.
  • Rules fire safety(PPB).
  • Labor protection instruction.
  • The order of operation of treatment plants.
  • Rules for the reception and release of petroleum products.
  • Cash register operation manual.

In addition, the modern realities of universal computerization require that the operator possess at least the initial user skills.

2.3 The direct manager of the gas station operator is the manager of the gas station, and direct supervision during the shift is carried out by its head.

2.4 During the work shift, the operator is strictly forbidden to leave workplace, except for the time intervals established by the approved daily routine (break for eating, technological breaks for equipment maintenance, etc.).

2.5 Filling station operator - a person carrying liability in case of shortage of oil products, financial resources, as well as in case of complete or partial loss (through his fault) of the functional conditions of the equipment and other property of the gas station.

2.6 The operator taking over the shift is obliged to:

  • check the compliance of the documentation at the workplace with the approved list;
  • make sure that the technological and cash register equipment, tools and materials;
  • accept the rest of the oil products from the shifter and fill out the acceptance sheet, indicating the meter readings and the level marks in the storage tanks;
  • to accept funds from the account at the cash desk of the gas station by making an appropriate entry in the cash book;
  • check the sanitary condition of the operator's room and the territory of the gas station.

Comments identified as a result of the above activities are reflected in the shift journal. The signature of the operator-cashier of the gas station on the acceptance of the shift confirms the imposition of personal responsibility on him, including material, for what is happening at the gas station.

During a shift, the operator's responsibilities include:

  • Ensuring the uninterrupted supply of petroleum products to the consumer.
  • Maintaining order in the premises and on the territory of the gas station.
  • Compliance with the procedure for receiving incoming motor fuel, including:

Study of accompanying documentation;

Checking the level of oil products in the incoming tank;

Termination of trade in the relevant type of fuel (by notifying customers by means of an information plate);

Measurement of the level in the storage tank before draining and recording in the corresponding section of the log;

Fuel drain;

Measurement of the level in the storage tank after draining and recording in the corresponding section of the log;

Entering data into the fuel receipt log;

Resumption of fuel sales.

  • Collection and transfer of funds to the collection team in accordance with the approved instructions.
  • In the event of a malfunction of the gas station equipment - organization of a call for a repairman and a message to the shift supervisor (gas station manager).
  • In the event of a power outage - a message to the duty service of the supplier organization and the shift supervisor (gas station manager).
  • In the event of an emergency situation (fire, flood, traffic accident, robbery, etc.) - organization of notification of the relevant services and the shift supervisor (gas station manager).
  • Reflection in the shift log of all incidents that occurred during the shift.

At the end of the work shift, the gas station operator transfers the shift in accordance with the algorithm described above and fills out the shift reporting forms transmitted (together with the final cashier's check) to the control of the manager of the gas station.

Video - Gas Station Operator Simulator

Petrol station operator training

The vast majority of companies (OOO Lukoil, Trade House Neftmagistral, Gazpromneft, Trassa Group of Companies, etc.) that own gas stations in the Russian capital prefer to fill the existing vacancies of gas station cashier operators with applicants who have gas station operator certificates. That is why, applicants who agree with the proposed level wages, and it is in a fairly wide range (from 20,000 to 40,000 Russian rubles), it is proposed to undergo preliminary training or retraining. In addition, for the gas station operator, training includes internships and training programs.

Briefly about the work and duties of the gas station operator

The work of a gas station operator is complex and responsible. This is due to a large number of labor functions that require increased concentration and attention, as well as the fact that the employee is in constant contact with customers and performs cash settlements.

The main responsibilities of the gas station operator include:

This is a general and far from complete list of labor duties of a gas station operator. Full list official duties The filling station operator is established in his job description - an internal document that each organization develops independently based on the characteristics of its work.

The structure of the job description for the operator of the gas station

The structure of the job description is not established by law, therefore, the instructions of different companies for the same position may differ both in terms of the list of requirements for a candidate for a vacancy, and in terms of the list of employee duties and other significant provisions. However, the structure in most cases remains general, defined by the rules personnel office work. Employers, when developing job descriptions for their employees, try to use this particular form because it allows you to take into account all important points work of a specialist in the company.

Don't know your rights?

What does she represent? Typical job description for the gas station operator includes the following main parts:

  1. General provisions. This section contains the basic conditions that determine the labor activity of the gas station operator in specific organization. Among these conditions:
    • required education;
    • experience;
    • professional skills;
    • legislative and local documents with which the employee must be familiarized before starting work.

    In addition, the same part of the instructions establishes the rules for the admission, dismissal and replacement of an employee, determines the place staff unit in the organizational and staffing table and the immediate supervisor of the employee is appointed.

  2. Official rights and obligations. Labor law obliges the employee to perform only those labor functions that are attached to him employment contract and job description (i.e., the employee has the right not to perform any other assignments). That is why this part of the instruction is the main one in the document and requires a careful and balanced approach during development. The more detailed and fuller the duties and rights of the gas station operator are defined, the easier it is for the employee to work and the more efficient his work will be.
  3. Responsibility. This part specifies, in comparison with the legislation, the list of violations for which an employee can be punished.

Standard requirements for a candidate for the position of a gas station operator

None special education for applicants for the position of a gas station operator is not required. Rather, here we can talk about a certain set of professional and personal qualities. And if personal qualities are assessed, as a rule, at a job interview, then a list of the necessary professional skills of an employee can be entered in the job description of the gas station operator.

So, the gas station operator should know:

  • rules for working with refueling equipment;
  • the procedure for working with a cash register;
  • the procedure for the operation of the gas station treatment plant;
  • the procedure for receiving and dispensing fuel;
  • fire safety standards at gas stations;
  • labor protection rules at gas stations.

However, an employee can be trained in all these skills directly at the workplace, therefore, as a rule, work experience from candidates for the position of a gas station operator is not required.

Typical terms of reference for a gas station operator

The standard job responsibilities of a gas station operator can conditionally be divided into 3 groups:

  • responsibilities when accepting a shift;
  • duties during the shift;
  • duties at the end of the shift.
  1. When taking a shift, the operator must:
    • check the serviceability of the equipment, the availability of materials and tools necessary for the work;
    • check the completeness of the working documentation;
    • accept the fuel available in the tanks, fixing the volume and meter readings in the report;
    • accept cash at the cash desk;
    • evaluate the order in the working room and on the territory of the gas station.
  2. While on duty, the operator must:
    • deliver fuel to customers;
    • carry out regular cleaning on the territory of the gas station and in the working room;
    • accept incoming fuel in the manner approved by the documents of the enterprise;
    • transfer funds to collectors at the appointed time;
    • upon detection of malfunctions in the equipment of the gas station, cash register and other equipment, immediately report this to the responsible person and call the master;
    • in the event of an emergency, contact the relevant services (police, firefighters, the Ministry of Emergency Situations, etc.) and call the head;
    • be constantly at work.
  3. At the end of the shift, the operator must:
    • provide an explanatory note in case of emergency situations that occurred during the duty;
    • transfer duty to the shifter, fixing the transfer in the shift log.

The typical terms of reference for a gas station operator given here do not take into account the specifics of the work of a particular gas station, therefore, when developing a job description and establishing the job responsibilities of an employee, any employer can start from the list we have given, taking into account the realities of the work of their enterprise.

Responsibility of the gas station operator

This section of the instruction may contain both a simple mention that the operator, as a materially responsible person, is liable in accordance with the law, and a list of specific penalties for certain misconduct. However, when working on this part of the document, it must be remembered that it is impossible to establish liability conditions more stringent than those provided for by law.


^ 3 Job description of the senior operator of gas filling stations

^ I General provisions

1.1 The senior operator of the gas filling station belongs to the category of workers.

1.2 Appointment to the position of the senior operator of the gas filling station and dismissal from it is carried out by order of the head of the gas filling station on the proposal of the foreman.

1.3 The senior operator of the filling station in his work observes:

Rules for accounting for LPG and the procedure for maintaining accounting documentation;

1.4 The senior operator of the gas filling station is directly subordinate to the master.

^ II Responsibilities

2.1 The senior operator of the filling station is obliged to:

Follow all orders and instructions of the master;

Perform work in accordance with the production instructions and regulations for refueling LPG gas-balloon vehicles;

^III Rights

3.1 The senior operator of the filling station has the right to:

^ IV Responsibility

4.1 The senior operator of the filling station is responsible for:

Interchangeable master

(signature)

(surname, initials)

Familiarized with the instructions:

(signature)

(surname, initials)

^ 4 Job description of the operator for filling gas-balloon vehicles at gas filling stations (hereinafter referred to as the Filler)

^ I General provisions

1.1 Filler AGZS belongs to the category of workers.

1.2 Appointment to the position of a gas filling station filler and dismissal from it is carried out by order of the head of the gas filling station on the proposal of a shift foreman.

1.3 The gas filling station filler in its work observes:

Rules for safe operation technological equipment and instrumentation and A used at gas filling stations;

Internal labor regulations.

1.4 The AGZS filler is directly subordinate to the shift foreman.

^ II Responsibilities

2.1 The gas filling station filler is obliged to:

Follow all orders and instructions of the shift foreman;

Carry out work in accordance with the production instructions and the regulations for refueling LPG gas-balloon vehicles. Maintenance by one operator of no more than two gas filling columns at the same time is allowed;

Strictly follow the rules for the operation of process equipment, safety and fire safety rules;

Comply with the internal regulations established at the gas filling station.

^III Rights

3.1 The gas filling station filler has the right to:

Get acquainted with the draft decisions of the management of the gas filling station related to its activities;

Require management to ensure security measures, compliance with the necessary sanitary and living conditions relating to its activities;

Require PPE, workwear, safety shoes and safe tools from management;

Make suggestions for improvement production activities within the scope of their competence.

^ IV Responsibility

4.1 The gas filling station filler is responsible for:

Interchangeable master

(signature)

(surname, initials)

Familiarized with the instructions:

(signature)

(surname, initials)

^ 5 Job description of a repairman for maintenance of technological equipment at a gas filling station (hereinafter referred to as a repairman of a gas filling station)

^ I General provisions

1.1 The gas filling station repairman belongs to the category of workers.

1.2 Appointment to the position of a gas filling station repairman and dismissal from it is carried out by order of the head of the gas filling station on the proposal of a shift foreman.

1.3 The gas filling station repairman in his work observes:

Rules for the safe operation of process equipment used at gas filling stations;

Internal labor regulations.

1.4 The gas filling station repairman directly reports to the shift foreman.

^ II Responsibilities

2.1 The gas filling station repairman is obliged:

Perform work in accordance with production instructions: for the maintenance and safe operation of pressure vessels, for the maintenance and safe operation of pumps and compressors pumping LPG, for the operation of instrumentation and automation, for the maintenance and safe operation of process gas pipelines, fittings and utilities, for the maintenance and safe operation of ventilation systems, for the discharge of LPG from the tanks of autogas carriers into the tanks of gas filling stations;

Maintain operational production documentation;

2.2 Comply with the internal regulations established at the gas filling station.

^III Rights

3.1 A gas filling station mechanic has the right to:

Get acquainted with the draft decisions of the management of the gas filling station related to its activities;

Require management to ensure security measures, compliance with the necessary sanitary and living conditions relating to its activities;

Require PPE, workwear, safety shoes and safe tools from management;

Make proposals for improving production activities within its competence.

^ IV. Responsibility

4.1 The gas filling station repairman is responsible for:

For improper performance or non-performance of their official duties provided for by this job description - within the limits determined by the current labor legislation of the Republic of Uzbekistan;

For offenses committed in the course of carrying out their activities - within the limits determined by the current administrative, criminal and civil legislation of the Republic of Uzbekistan;

For causing material damage - within the limits determined by the current labor and civil legislation of the Republic of Uzbekistan.

Interchangeable master

(signature)

(surname, initials)

Familiarized with the instructions:

(signature)

(surname, initials)

^ 6 Job description of an electrician AGZS (hereinafter - an electrician AGZS)

^ I General provisions

1.1 The gas station electrician belongs to the category of workers.

1.2 Appointment to the position of a locksmith and dismissal from it is carried out by order of the head of the gas filling station on the proposal of a shift foreman.

1.3 The gas filling station electrician in his work observes:

Rules for the installation of electrical installations, rules for the technical operation of electrical installations of consumers and safety rules for the operation of electrical installations of consumers in the scope of the position held;

Rules for the safe operation of process equipment used at gas filling stations;

Internal labor regulations.

1.4 The gas filling station electrician reports directly to the shift foreman.

^ II Responsibilities

2.1 The gas filling station electrician is obliged to:

Possess knowledge and skills in accordance with the Unified Tariff - qualification handbook works and professions of workers and perform work in accordance with the production instructions for the operation of electrical equipment, instrumentation and A - carry out external examination electrical equipment (the condition of the input of wires and cables in electrical equipment, the integrity of glass lamps, the state of grounding, the operation of the ventilation of the backwater of rooms with electrical equipment and instrumentation and A, the presence of warning inscriptions and design marks on electrical equipment, the temperature of the outer surfaces of the housing, the integrity of fasteners), preventive tests, repair of electrical equipment;

Maintain operational production documentation;

Strictly follow the rules for the operation of process equipment, safety and fire safety rules.

Comply with the internal regulations established at the gas filling station.

^III Rights

3.1 The gas station electrician has the right to:

Get acquainted with the draft decisions of the management of the gas filling station related to its activities;

Require management to ensure security measures, compliance with the necessary sanitary and living conditions relating to its activities;

Make proposals for improving production activities within its competence.

^ IV. Responsibility

4.1 The gas filling station operator is responsible for:

Correct and safe operation of electrical equipment at gas filling stations;

Improper performance or non-performance of their official duties provided for by this job description - within the limits determined by the current labor legislation of the Republic of Uzbekistan;

Offenses committed in the course of carrying out their activities - within the limits determined by the current administrative, criminal and civil legislation of the Republic of Uzbekistan;

Causing material damage - within the limits determined by the current labor and civil legislation of the Republic of Uzbekistan.

Interchangeable master

(signature)

(surname, initials)

Familiarized with the instructions:

(signature)

(surname, initials)

Appendix 5

To the "Rules of technical and

Safe operation

List of basic instructions for gas filling station personnel

I Job descriptions


  1. Head of gas station

  2. Shift foreman

  3. Senior Operator

  4. filler

  5. Locksmith - repairman for maintenance of technological equipment

  6. Locksmith - electrician

II Instructions


  1. Maintenance and safe operation of pressure vessels

  2. Maintenance and safe operation of pumps and compressors pumping LPG

  3. Maintenance and safe operation of filling and drain dispensers

  4. For the operation of electrical equipment

  5. Operation of instrumentation and automation

  6. Maintenance and safe operation of technological gas pipelines, fittings and utilities

  7. Maintenance and safe operation of ventilation systems

  8. By draining the SU from the tanks of autogas carriers into the tanks of the gas filling station

  9. For refueling LPG gas-balloon vehicles

  10. For carrying out repair work inside tanks, apparatuses, process gas pipelines

  11. For carrying out hot and gas hazardous work

  12. Providing first aid to those affected by the effects of LPG

Appendix 6

To the "Rules of technical and

Safe operation

Autogas filling stations (AGZS)»

^ Typical production instructions for refueling LPG cylinders of gas-balloon vehicles

This instruction has been developed for service personnel for refueling cylinders of gas-cylinder vehicles in accordance with the requirements of current regulatory documents.

On the basis of this Instruction, the corresponding production instruction must be developed and approved by the management of the gas filling station.

Personnel performing operations for filling car cylinders with liquefied gas must clearly know and strictly comply with all the requirements set forth in the production and job instructions.

Near the filling stations on the stand under the glass should be hung out:

Instructions for refueling LPG gas-balloon vehicles;

Warning posters and inscriptions “Flammable”, “No smoking”, etc.

When refueling, the driver of a gas-balloon car must follow all the instructions of the gas filling station service personnel.

The driver of the car arriving at the gas station must have the following documents with him for presentation to the gas filling station employees:

A waybill with a note from the mechanic of the enterprise about the serviceability of gas-balloon equipment and a permit for refueling (except for vehicles individuals);

Registration with authorities public service security traffic Ministry of Internal Affairs of the Republic of Uzbekistan on the conversion of a car to gas equipment;

Certificate for the right to use gas-cylinder equipment, issued specifically authorized body state supervision with an indication of the period of its validity.

Before the car enters the territory of the filling station for refueling, the driver must:

Disembark passengers;

Move at a speed not exceeding 5 km/h;

Stop at a stop sign, which must be placed in front of the filling station at a distance of at least 20 m from the filling station;

Stop at the gas station only at the command of the filler and turn off the engine.

Before starting refueling after the car is installed in the filling box indicated by the filler, the driver is obliged to present to the filler all Required documents. In case of detection of violations in the execution of documents, their absence or invalidity of any of them by the validity period, the filler is obliged to immediately send the car outside the territory of the gas filling station.

Before filling a certified or new cylinder, purge with liquefied gas vapours.

Refueling a gas-balloon car should be carried out in the following sequence.

After checking the documents by the filler, the driver must: remove the key from the ignition; install a manual parking brake; leave the cabin; open the rear and front hoods.

The filler must:

visually inspect technical condition LPG equipment and the technical condition of the car, while paying attention to: the date of the next survey; the presence of established inscriptions; serviceability of valves and valves; serviceability of the cylinder body (absence of shells, potholes, corrosion, dents); balloon fastening; change in the design of equipment; the presence of breaks in the insulation of electrical wiring and gasoline wiring of the car; the presence of leaks from the connections;

Close the flow valve for gas equipment car;

Remove the safety plugs from the filling nozzle;

Connect the filling hose to the filling fitting, make sure its connection is reliable;

Open filling valve;

Make sure that there is residual pressure in the cylinder;

Slowly open the valve on the filling head of the sleeve (clamp, filling nozzle);

Make sure there are no leaks in the connecting parts.

In case of its appearance, it is necessary to immediately close the tap on the filling clamp and the filling valve, reconnect the filling hose to the filling fitting and repeat the last three operations.

If a leak is found in other places caused by damage to the equipment, it is necessary to immediately stop refueling and remove the car from the territory of the filling station aids without starting the engine.

After filling the cylinder according to the application of the driver, determined by the display of the filling station, the filler must:

Close the valve on the gas filling hose;

Close the filling valve on the vehicle;

Disconnect the gas-filling hose of the column from the filling fitting of the gas-cylinder installation of the car;

Install safety plugs on the filling nozzle;

Inform the driver about the completion of refueling the car.

The driver, having received a command from the filler about the end of refueling, is obliged:

Slowly open the flow valve;

Make sure that there are no leaks in the gas-balloon equipment of the car;

Start the engine and make sure there is no leakage under the hood of the car;

Drive the car away from the filling station to a safe distance;

Make a full payment for refueling with the operator according to the values ​​​​of the counter for accounting for refueling gas;

Receive from the operator a check of the cash register for the amount of the supplied amount of gas.

If after the end of refueling and starting, the engine gives interruptions (pops), it must be immediately turned off and the car removed from the territory of the filling station by auxiliary means.

During the filling of the balloon, the filler must:

Strictly monitor the exact filling of the cylinder, avoiding its overflow. An overfilled cylinder must immediately be emptied of excess LPG;

Monitor the LPG pressure on the pressure gauge on the column, not allowing it to exceed more than 1.6 MPa (16 kgf / cm 2);

Do not hit the balloon.

In the event of emergencies at the time of refueling (when the pressure on the dispenser rises above 1.6 MPa (16 kgs/cm 2), when a leak is detected during the filling of a car cylinder, at filling dispensers, when the filling hose breaks, etc.), necessary:

Stop refueling immediately;

Close the filling valve on the car;

Close the filling valve on the filling hose;

If necessary, turn off the shut-off valves in front of the filling dispenser;

Turn off the pumping and compressor equipment;

Prohibit the entry of cars to the columns and the inclusion of car engines;

Report the incident to the shift supervisor.

In case of emergencies, it is necessary to act in accordance with the Accident Elimination Plan at the gas filling station.

General provisions
Automobile gas filling stations (AGFS) supplying vehicles with liquefied hydrocarbon gases (LHG) with an overpressure of not more than 1.6 MPa, used as automotive fuel, are classified as hazardous production facilities, and activities for their design, construction, expansion, reconstruction, technical re-equipment , conservation and liquidation, as well as the manufacture, installation, adjustment, maintenance and repair of used gas filling stations technical devices regulated by the Federal Law "On Industrial Safety of Hazardous Production Facilities" dated July 21, 1997 N 116-FZ<*>and the General Industrial Safety Rules for organizations operating in the field of industrial safety.
The operation of automobile gas filling stations (AGFS) is carried out by organizations that have trained and duly certified personnel, the necessary material and technical base, as well as a license from the Gosgortekhnadzor of Russia for the operation of an explosive facility.
At each filling station, job descriptions and production instructions are developed, and a filling station passport is drawn up.

Personnel training and admission
Persons who are trained, certified and have a certificate for the right to service gas filling stations can be allowed to service gas filling stations.
Training programs should be drawn up on the basis of standard programs agreed with the Gosgortekhnadzor of Russia.
Individual training of personnel is not allowed.
Certification of gas filling station operators is carried out by a commission with the participation of an inspector of the Gosgortekhnadzor of Russia. Persons who have passed certification must be issued certificates signed by the chairman of the commission and the inspector of the Gosgortekhnadzor of Russia.
Periodic testing of the knowledge of the personnel servicing the gas filling station should be carried out at least once every 12 months.
Extraordinary examination of knowledge is carried out:
a) upon transfer to another organization;
b) by decision of the administration or at the request of the inspector of the Gosgortekhnadzor of Russia.
The results of an extraordinary examination of the knowledge of the service personnel are documented in a protocol signed by the chairman and members of the commission with a mark in the certificate.
In case of a break in work in the specialty for more than 12 months, the personnel servicing the gas filling station, after checking their knowledge, must undergo an internship before being allowed to work independently to restore practical skills according to a program approved by the management of the organization.
The admission of personnel to self-service gas filling stations must be issued by order of the organization.
The admission of personnel to independent maintenance of vessels is issued by order of the organization.
What is pressure?
Pressure is the force acting per unit area. The pressure is denoted by the Latin letter R.
P = F/S,
where F is the force, N (kgf);
S - area, m 2 (cm 2).
Pressure can be: atmospheric (barometric), absolute (true), excess (gauge).
Atmospheric pressure is the pressure exerted by the atmosphere on all objects in it. It is balanced by a column of water with a height of 10m33cm or a column of mercury with a height of 760mm at a temperature of 0 o C. It is also called the physical atmosphere and is denoted: atm (1atm = 760mm Hg = 101080Pa)
Absolute pressure is the sum of atmospheric pressure and gauge pressure.
Rabs = Ratm + Rizb
For example, the pressure in a boiler, tank, or cylinder plus the pressure of the ambient air. Absolute pressure is measured in kgf / cm 2 (MPa).
Excess pressure is the pressure of steam inside a boiler or gas inside a cylinder, tank, without taking into account the pressure of the surrounding air. Excess pressure is measured and denoted by kgf/cm 2 (MPa).
In a technical system, an atmosphere (at) is taken as a unit of pressure - this is a force of one kilogram acting on an area of ​​\u200b\u200bone square centimeter (1at \u003d 1kgf / cm 2).

Physical and chemical properties of liquefied gas
Combustible gases used in vehicles are of two types:

      natural;
      artificial.
The source of obtaining a propane-butane mixture (С3Н8 - propane; С4Н10 - butane) is oil. Propane-butane mixture (PBS) belongs to the group of liquefied gas, because with an increase in pressure and a decrease in temperature, it passes into a liquid state with a multiple decrease in volume (250 times). The boiling point of propane is minus 42°C, and the boiling point of butane is minus 0.5°C.
PBS must meet the requirements of GOST 27578-87:
1. winter mixture PA (auto) 90±10% propane;
2. PbA summer mixture (auto) 50±10% propane, and the rest is butane;
3.liquefied gas should be smelled when the room is gassed
0.5% by volume;
4. liquefied gas is purified from hydrogen sulfide, leaving it 0.003% by volume.
5. The upper explosive limit of ERW is the maximum content of combustible gas in a mixture with air at which an explosion from an external source of ignition is possible.
Lower explosive limit LEL - the minimum content of combustible gas in a mixture with air at which an explosion from an external source of ignition is possible.
Explosive limits:
Propane: 2.3 - 9.5%
Butane: 1.9 - 8.5%
6. Gas density - propane = 2 kg / m 3; butane \u003d 2.7 kg / m 3
7. Relative density is the density of a gas relative to the density of air:
proran = 2: 1.29 = 1.55, butane = 2.7: 1.29 = 2.01

POSITIVE PROPERTIES OF LIQUEFIED GAS
Positive properties regarding gasoline:

    gas is cheaper;
    the car works environmentally friendly, CO is less;
    higher octane rating than gasoline
    oil changes less often, i.e. less polluted;
    convenient for transportation, because from one volume of liquid, 250 times more gas formation is obtained.
NEGATIVE PROPERTIES OF LIQUEFIED GAS
    when the room is filled with liquefied gas vapor from 2-9% of the volume and when a source of fire is introduced, an explosion will occur
    in the event of a gas leak without a source of fire, liquefied gas vapors fill the lower layers of the room, because By specific gravity 2 times heavier than air. A person in such an atmosphere dies of suffocation;
    liquefied gas during incomplete combustion releases carbon monoxide (CO-carbon monoxide), which has a negative effect on the human body, because. CO combines with the blood faster than oxygen. 1% CO is a lethal dose for humans. Asphyxiating gas is a leak, and poisoning occurs when the gas is burned, i.e. substances released during the combustion of liquefied gas.
    Liquefied gas has a large coefficient of volumetric expansion compared to water, 11-16 times higher. Therefore, gas storage vessels are filled to 85% to avoid their bursting pressure.
    Liquefied gas in contact with open area body in a liquid state freezes this area due to the absorption of heat. This is called a chemical burn. Rinse with plenty of cold water
Design features of AGZS.
The stationary gas filling station contains a stationary tank 1, a gas dispenser 7, a centrifugal pump 22 connected to the tank and a column, a control panel 17, as well as a system for draining, suction and injection of LPG.
The stationary tank 1 is equipped with two safety valves 3 located in its upper part, a pressure gauge and an LPG level indicator, connected to the control panel 17. The LPG drain system contains a transport tank 2, which is connected to the stationary tank through drain and equalizing hoses.

The suction system includes a pump 22 with an electric motor 20 connected through an electrical circuit with a control panel 17, and a suction line equipped with a shut-off valve 26, a pressure gauge 25, a gas filter 24 and a pressure gauge 23.
The injection system contains a pipeline 8 with an electric valve 6 connected to the control panel, and an oil separator 19.
The geyser 7 has a base 11 placed on a rigid foundation 12, an electric gauge 18, a gas meter 10 indicating the amount of gas filled and its cost, a degasser 9, a pressure regulator 16 and a flexible hose 14 with a filling device 13.
The degasser 9 ensures the separation of the liquid and gaseous phases of LPG. The vapor phase enters the pipeline 4 and returns to the stationary tank 1. The pressure regulator 16 is equipped with a high-speed valve 15 and communicates with the degasser 9 and the filling hose.
Safety valve 3 ensures that the vapor phase is discharged into the atmosphere. Line 8 liquid phase electric pump unit H4-5/170-1 is equipped with two shut-off valves. Line 4 of the vapor phase AGZS contains a mechanical valve and an electric valve communicated with the control panel 17.
The principle of operation of AGZS is as follows. Siv gas from a mobile tank is carried out through a drain hose. The elimination of plugs is ensured by means of an equalizing hose.
During refueling of vehicles, LPG from a stationary tank 1 through an open valve 26 and a filter 24 enters the suction pipe of the centrifugal pump and then through the discharge pipeline 8 through the degasser 9 and gas meter 10, pressure regulator 16 to the filling hose column 7.
The required suction height of the centrifugal pump 22 is provided by an AB-15 type compressor. The compressor creates excess pressure in the tank
0.1-0.2 MPa higher than the vapor pressure of the pumped gas. Pressure gauges 5.25 and return line 21 are used to control and regulate the process.
Liquefied gas from the transport tank 2 to the tank 1 of the station can be moved using a pump. In this case, the LPG is moved by creating an excess pressure of 0.1-0.2 MPa in the transport tank. To purify the LPG from oil that can get from the compressor 22, the station is equipped with an oil separator 19.
A typical stationary gas filling station contains four containers. The total volume of LPG storage is 100m 3 . the station can provide 600 fillings per day with three-shift operation. The maintenance staff of the station consists of 25 people. The area occupied by the station is 5300m 2 . LPG is drained and filled with gas-balloon cars separately.

Operation of technological gas pipelines, fittings
and engineering communications
Technological gas pipelines and fittings must be inspected every shift by a mechanic on duty in order to detect gas leaks. Leakage points should be sealed immediately in accordance with the manufacturer's instructions. A gas leak can be detected by ear or by freezing of a defective area. Small leaks are detected at operating gas pressure using a soap emulsion; at negative temperatures, alcohol is added to the soap emulsion. Explosion-proof devices intended for this purpose may be used.
It is forbidden to detect gas leaks with an open flame.

Maintenance of gas pipelines and fittings is carried out in the following terms:
inspection of all external gas pipelines and fittings in order to identify and eliminate malfunctions and gas leaks - monthly;
checking for tightness at operating pressure of all threaded and flanged connections of pipelines and fittings, stuffing box seals located in the room - monthly;
checking the gas contamination of the wells of all underground utilities within the territory of the gas filling station - according to the schedule approved by the head (technical manager) of the organization.
In addition to the above works, it is necessary to check the serviceability of the drive to the shut-off valves, restore license plates and indicators of the direction of valve opening.
Faulty and leaky fittings that are not suitable for further operation must be replaced.
The operation and serviceability of safety spring valves installed on gas pipelines, tanks and equipment of gas filling stations should be checked at least once a month by opening them for a short time.
The setting pressure of safety relief valves should not exceed by more than 15% the working pressure in tanks and gas pipelines. It is forbidden to operate process equipment, tanks and gas pipelines with faulty and unadjusted safety relief valves. Checking the settings of the valves, their adjustment should be carried out on the stand or on site using a special device.
Check frequency:
for safety relief valves of tanks - at least once every 6 months;
for other relief valves - when carrying out current repair but at least once a year.
The valves are sealed after the test, the test results are reflected in the journal.
A serviceable safety relief valve must be installed in place of a valve removed for repair or inspection.
The term for the current repair of gas pipelines is determined by the results of the inspection.

Filter Valve three-way flanged

Maintenance of shut-off valves is carried out at least once a year
The results of checking and repairing valves must be recorded in a log.
Capital repairs of gas pipelines are carried out as needed.
replacement of movable and fixed supports.

Check valve Ball valve

During the overhaul of gas pipelines, all types of work provided for the current repair and maintenance should be carried out. After a major overhaul, gas pipelines must be tested in accordance with the requirements of the "Safety Rules in the Gas Industry".
The frequency of the current repair of engineering networks is established:
external networks of water supply and sewerage - 1 time in 2 years;
external heating networks - 1 time per year;
internal networks of water supply, heating, etc. - 1 time in 2 years.
Sleeves used in draining and filling operations should not have cracks, cuts, swellings and scuffs. If there is one of the indicated defects on the sleeves, the sleeves are replaced with new ones. The hoses are subjected to a hydraulic strength test with a pressure equal to 1.25 working pressure once every 3 months. The test results are recorded in the journal.
Each sleeve must have a tag, which must indicate the serial number, the dates of the conduct (month, year) and the subsequent hydrotest (month, year).
Metal-cord and rubber-fabric sleeves must be protected from static electricity. Rubber-fabric sleeves must be wrapped with copper wire with a diameter of at least 2 mm or a copper cable with a cross-sectional area of ​​​​at least 4 mm with a turn pitch of not more than 100 mm. It is forbidden to tighten the union nuts of the hoses, disconnect the hoses under pressure, and also use an impact tool when screwing on and unscrewing the nuts.
Operation of tanks.
Tanks must be checked for overpressure before filling. The excess pressure in the tank must be at least 0.05 MPa (0.5 kgf/cm2). The tanks must be put into operation after examination and repair on the basis of the written permission of the head of the filling station.
During the operation of the tanks, maintenance and technical certification should be carried out. During the maintenance of tanks, the following work should be performed every shift:
inspection of tanks and fittings in order to identify and eliminate malfunctions and gas leaks;
checking the gas level in the tanks.
Gas leaks that occur during operation must be repaired immediately.

Faults found during maintenance should be recorded in a log.
In case of detection of malfunctions that can lead to disruption of technological processes, measures provided for by production (technological) instructions should be taken. If during the maintenance of the tanks, faults are found that cannot be immediately eliminated, then the faulty tank must be disconnected from the gas pipelines and equipment by installing plugs with protruding tails.
Serviceability of safety valves must be checked in accordance with the requirements of the Rules. Installing a plug in place of a valve being removed for inspection or repair is prohibited.

According to the schedule approved by the management of the gas station organization, the following work should be performed:
checking safety valves for operation at setting pressure;
inspection, lubrication and acceleration of the worm of valves, taps and valves;
draining condensate from tanks through drainage devices (as needed).
A complete inspection of tanks with fittings and instrumentation in working condition with a log entry is carried out by a person responsible for the good condition and safe operation of pressure vessels at least once every 3 months.

Operation of compressors, pumps, evaporators
When operating compressors, pumps and evaporators, it is necessary to comply with the requirements of production instructions, instructions of manufacturers. When the pressure on the discharge lines of compressors, pumps and evaporators is higher than that provided for by the project, the electric motors and evaporator coolants should be automatically turned off.
It is forbidden to operate compressors, pumps and evaporators with faulty or switched off ventilation, with faulty instrumentation or in their absence, if there is a gas concentration in the room that exceeds 20% of the lower flammable limit of the gas. Information about the mode of operation, the number of hours worked by compressors, pumps and evaporators, as well as noticed malfunctions in operation, should be recorded in the operating log. The withdrawal of compressors, pumps, evaporators from the operating mode to the reserve must be carried out in accordance with the production (technological) instructions. After stopping the compressor, pump, turning off the evaporator, the shut-off valves on the suction and discharge lines must be closed. The air temperature in the pump-compressor and evaporator compartments in work time should not be lower than +10 °C. If the air temperature is below +10 °C, it is necessary to drain the water from the water supply system and from the cooling system of the compressors and the heating system of the evaporators in order to prevent water from freezing after stopping the compressors and evaporators.

Compressor plant

In the pump-compressor and evaporator compartments, there should be technological schemes of equipment, pipelines and instrumentation, installation operating instructions and operational logs.
During the maintenance of compressors and pumps, the following works are carried out every shift:
inspection of units, shut-off and safety valves, measuring instruments and automation in order to identify malfunctions, technical condition and gas leaks;
cleaning equipment and instrumentation from dust and dirt, checking the availability and serviceability of grounding and fastenings;
control over the absence of extraneous noise, characteristic vibrations, bearing temperature, level, pressure and temperature of oil and cooling water;
checking the serviceability of moving parts accessible for inspection;
control over the serviceable condition and correct position of stop valves and safety valves;
compliance with the requirements of the instructions of equipment manufacturers;
shutdown of faulty equipment.
The gas pressure in the compressor discharge gas pipeline must not exceed the condensing pressure of LPG vapor at the discharge temperature and be higher than 1.6 MPa (16 kgf/cm2). The gas pressure at the suction line of the pump must be 0.1-0.2 MPa (1-2 kgf/cm2) higher than the saturated vapor pressure of the liquid phase at a given temperature.
The pumps should be serviced monthly.
For maintenance:
During ongoing repairs
Compressors and pumps must not be operated with an immediate stop in the following cases:
gas leaks and malfunctions of valves;
the appearance of vibration, extraneous noise and knocks;
failure of bearings and stuffing box seal;
failure of the electric drive, starting fittings;
malfunctions of coupling joints, V-belts and their guards;
increasing or decreasing the set gas pressure in the suction and pressure gas pipeline.

The operation of evaporators is prohibited in the following cases:
with an increase or decrease in the pressure of the liquid and vapor phases above or below the established norms;
in case of malfunction of safety valves, instrumentation and automation equipment or in their absence;
with unverified instrumentation;
in case of incomplete quantity or malfunction of fasteners;
upon detection of gas leakage or sweating in welds, bolted joints, as well as violation of the integrity of the evaporator structure;
when the liquid phase enters the gas pipeline of the vapor phase;
when the coolant supply to the evaporator is interrupted.

Operation of ventilation systems
At the filling station, operating instructions for the ventilation system should be developed. Each ventilation system must have a designation and serial number. A passport must be drawn up for each ventilation system. In the event of a malfunction of the ventilation systems and insufficient air exchange in the production premises, work with liquefied gases at the gas filling station is prohibited until the malfunction is eliminated. In the premises of gas filling stations with the production of category "A", the devices installed according to the project, signaling a dangerous concentration of gas in the room, must be operational. In case of their temporary inoperability (no more than 72 hours), it is necessary to analyze the air in the gas filling station premises for the content of gases in them with portable gas analyzers every 30 minutes during the working shift. and eliminate the causes of the jumper. Start-up of exhaust ventilation systems should be carried out 15 minutes before the start of operation of the process equipment, then the supply ventilation systems are turned on.
Maintenance of ventilation chambers and ventilation systems every shift. results Maintenance should be recorded in the operating log.
Operation of electrical equipment
. The operation of electrical equipment and electrical installations must be carried out by trained operational electrical personnel who have passed a knowledge test in accordance with the requirements of the "Rules for the operation of electrical installations of consumers", having an electrical safety group of at least IV and a certificate of the established form.
Operation of automation devices and instrumentation
Instruments and devices of automatic safety, automatic control and instrumentation installed on gas pipelines and gas filling station equipment must pass:
Maintenance;
repair;
verification of serviceability and correctness of indications;
checking the operation of protection devices, interlocks and alarms;
state trust.
.
Simultaneous maintenance of instrumentation and automation with maintenance of gas pipelines, equipment, tanks and electrical equipment is allowed. Gas station personnel are not allowed to open the devices.
The identified malfunctions in the operation of measuring instruments and automation are reported to the shift (senior) foreman of the gas filling station.
Instrumentation maintenance includes the following:
external inspection of the device;
checking the serviceability of electrical wiring and other communications;
preservation of seals (if any);
detection of defects arising during operation;
lubrication of movement mechanisms;
change of chart paper, pens and ink in self-recording instruments, refilling of special liquids.
Instrument readings are recorded every shift. Checking the operation of alarm devices and safety automation interlocks should be carried out at least once a month.
Disabling automatic safety devices and interlocks is allowed only for a short period of time by written order of the gas filling station management with an entry in the log, subject to the creation of additional measures to ensure trouble-free and safe operation. If the automatic gas contamination detector fails, it must be replaced with a backup one. Prior to replacement, it is necessary to control the concentration of gas in the air of industrial premises with portable gas analyzers every 30 minutes during the work shift.
.
Indicating pressure gauge with single-turn Electrocontact pressure gauge
Operation of buildings and structures
By order of the head of the gas filling station organization, a person responsible for the proper operation of buildings, fences and structures, compliance with the deadlines and quality of their repair, as well as for the good condition of roads, sidewalks, blind areas of buildings and landscaping of the gas filling station territory (watering, gardening, cleaning, etc.) It is necessary to monitor the appearance of cracks and damage as a result of vibrations, temperature effects and other causes.If cracks and damage are found in the walls and foundations, measures must be taken to eliminate them.After the cracks have been eliminated, it is necessary to monitor their possible further development. less than once a year, and reinforced concrete at least twice a year.If damage and malfunctions are found in buildings and structures, measures must be taken immediately to ensure their elimination.
At the gas filling station, constant monitoring of the state of the embankment and sprinkling above the tanks should be carried out. The embankment and the embankment above the underground tanks should be 0.2 m higher than their upper generatrix and not less than 6 m wide, counting from the tank wall to the edge of the embankment.
Violation of the embankment is allowed in exceptional cases with the permission of the fire authorities in connection with the work on laying and repairing communications. After completion of work, the embankment should be immediately restored. The territory of tank farms should be cleared of dry grass in summer and of snow in winter.
. It is forbidden to obstruct passages and driveways. The entire territory of the gas filling station must be kept clean and tidy. All roads, fire lanes and exits to public roads must be in good condition. Road ditches must be systematically cleaned to ensure normal stormwater runoff.
.
Warming of frozen water supply systems is carried out only with steam or hot water (the use of open fire is strictly prohibited).
Water supply and sewerage wells, located in a zone with a radius of 50 m from the buildings and structures of gas filling stations, must have double covers. The space between the covers must be covered with sand to a height of at least 0.15 m. No more than two workers are allowed in the wells at the same time, while the work must be carried out by them in life belts and hose gas masks. The use of open fire in wells is prohibited.
On the surface of the earth on the windward side there should be two people who are obliged to hold the ends of the ropes from the life belts of workers inside the well, continuously monitor them and prevent unauthorized persons from entering the place of work. When continuing work for more than one hour, it is necessary to periodically check the gas content and, if necessary, ventilate the well with a compressor or blower.

SAFETY REQUIREMENTS
AND FIRE SAFETY AT GFS
General provisions
At each gas filling station, instructions on labor protection (safety) should be drawn up and approved in accordance with the established procedure, establishing the rules for performing work and behavior in production premises and on the territory of the gas filling station. The instructions must contain fire safety requirements.
Responsible for general state Occupational safety at the gas filling station is the head of the organization.
Responsible for the implementation of the rules and instructions for the protection (safety) of labor during the performance of work are the supervisors of the work (senior foremen, foremen, etc.).
The management of gas filling stations is obliged to provide workers and employees with overalls, footwear and personal protective equipment of the required sizes in accordance with the nature of the work performed and standard standards. Personal protective equipment issued to workers should be checked and workers trained in its use.
The work manager is obliged to check the availability and serviceability of personal protective equipment for workers before starting work and instruct them additionally.
It is forbidden to fill LPG tanks by reducing the gas pressure in them by discharging the gas phase into the atmosphere.
Filling of automobile cylinders should be carried out no more than 90% of their geometric volume. Maintenance, repair, installation and dismantling of process equipment, tanks and gas pipelines may only be performed during the daytime. Works on localization and liquidation of accidents are carried out at any time by the personnel of the filling station. Tanks and gas pipelines must be freed from gas, unevaporated residues and carefully processed before starting repairs. Processing of tanks and gas pipelines should be carried out by steaming them and purging with an inert gas or filling them with warm water after disconnecting them from the vapor and liquid phase gas pipelines using plugs.
Dismantling of gas pipeline connections should be carried out after turning off the operating installations for protection against electrochemical corrosion, installing a shunt jumper and removing excess pressure in gas pipelines.
Do not retighten flange connections under pressure.
Plugs installed on gas pipelines must be designed for a pressure of at least 1.6 MPa (16 kgf / cm2). Plugs must have shanks protruding beyond the flanges. Liners must be stamped with indication of gas pressure and gas pipeline diameter. It is forbidden to install plugs made of steel of lower quality than the gas pipeline. If there are signs of the presence of gas, repair work should be immediately stopped, and workers removed from the danger zone. Repair work can be resumed only after the elimination and repair of gas leaks and confirmation by analysis of the absence of a dangerous concentration of gas in the air in the workplace.
Elimination of gas leaks on operating process equipment is prohibited.
Read all
Switching on of equipment and gas pipelines after maintenance or repair related to their shutdown and shutdown of gas should be carried out only with the written permission of the management of the enterprise (organization, etc.) of the gas filling station. Removal of plugs is carried out at the direction of the head of gas hazardous work after control pressure testing of the disconnected section of the gas pipeline and equipment. Welding must be carried out by a welder certified in accordance with the "Rules for the certification of welders", as well as who has passed the test of knowledge of safe working methods in the gas filling station gas facilities. Damaged sections of the gas pipeline and deformed flange connections must be replaced with new ones by welding coils. It is forbidden to install "patches", weld cracks, breaks and other defects.
The gas pipelines and fittings replaced during the repair must comply with the design ones. The use of pipes and fittings that do not have certificates is prohibited.
The use of open fire to eliminate blockages on the gas filling station gas pipelines is prohibited.
Before thawing a frozen section of the gas pipeline and after completion of work, it is necessary to conduct an external inspection of the gas pipeline. Areas with cracks, gaps must be turned off and blown through. The release of gas into the room is not allowed.
It is forbidden to open faulty fittings, make jerky openings, use levers in case of difficult stem travel, use impact tools when screwing in and unscrewing union nuts of hoses, tighten union nuts and disconnect hoses under pressure. During non-working hours, all shut-off valves on LPG pipelines must be closed. A serviceable safety valve must be immediately put in place of the safety valve removed for revision or repair. It is forbidden to install plugs instead of a valve.
The discharge of the vapor phase of LPG when purging gas pipelines must be carried out taking into account the maximum dispersion of gas in the atmosphere. It is not allowed to release LPG near buildings and structures or into unventilated areas of the adjacent territory.
It is forbidden to use sleeves connected from separate pieces.
If a dangerous concentration of gas occurs, it is necessary to stop work, ventilate the room, identify and eliminate the causes of gas contamination.
A dangerous concentration of gas in air is considered to be a concentration equal to 20% of the lower flammable limit of the gas.
Reception and transfer of a shift during the liquidation of an accident and during loading and unloading operations are prohibited.
Service personnel training
Specialists and workers involved in the operation of equipment, gas pipelines, as well as ventilation systems, electrical equipment, automation systems, alarms and instrumentation, primary fire extinguishing equipment, gas hazardous and hot work, must be trained in safe methods and techniques for performing work at gas filling stations before being assigned to independent work and pass the exam in the prescribed manner. Persons at least 18 years of age who have passed a medical examination in the prescribed manner are allowed to work at the gas filling station.
The primary test of knowledge of safety rules, safe methods and techniques for performing work at gas filling stations by persons, as well as chairmen and members of permanent examination commissions, should be carried out with the participation of a gas supervision inspector.
Re-testing of knowledge by workers - once every 12 months.
After checking the knowledge, each employee of the gas filling station, before being allowed to independently perform gas hazardous work, must undergo an internship under the supervision of experienced workers for ten work shifts.
Gas filling station employees must be instructed on safe working methods and techniques.

Starting and stopping process equipment
Start-up and shutdown of the technological equipment of gas filling stations must be carried out according to production instructions and with the permission of the senior or shift foreman.
The inclusion of gas filling stations after a break in operation for more than one shift should be carried out after inspection of process equipment, tanks and gas pipelines.
Before starting the process equipment of gas filling stations (compressors, pumps, evaporators), the following operations must be performed:
15 minutes before starting the equipment, turn on the supply and exhaust ventilation and check the degree of gas contamination of the room and explosive zones with a portable gas analyzer;
check the serviceability and tightness of equipment, fittings and gas pipelines;
check the serviceability of safety valves and instrumentation;
check the serviceability of starting and grounding devices;
check the presence and serviceability of the fences;
find out the reasons for the previous shutdown of the equipment (from the log) and, if the shutdown occurred due to any malfunction, make sure that this malfunction has been eliminated;
check for foreign objects interfering with the operation of the equipment;
check and, if necessary, tighten the anchor bolts (for compressors, pumps, evaporators, electric motors);
check the correct operation of the safety and interlocks.
Before starting the compressor, you must:
turn the crankshaft manually;
check the presence of oil in the crankcase;
put water into the cooling jacket;
make sure that the valves on the suction and discharge pipes of the compressors are closed, then open the shut-off valves on the discharge and suction manifolds;
remove the condensate from the liquid separator on the suction pipe of the compressor (by draining the condensate into a sealed container).
After turning on the compressor motor, you must:
make sure that the shaft rotates correctly in the direction of the arrow on the front cover of the crankcase;
when the nominal speed is reached, open the valve on the compressor discharge and gradually open the valve on the compressor suction.
When starting the compressor, make sure that there is no LPG liquid phase in the suction gas pipeline (check the operation of the condensate collector), the presence of which is manifested by knocking in the compressor or a sharp drop in suction temperature. In the event of knocking in the compressor, it is necessary to immediately stop the compressor and remove gas condensate from the supply gas pipeline, and then restart the compressor.
Stopping the compressor must be done in the following order:
close the shut-off valve on the compressor suction pipe;
stop the compressor motor;
after the shaft rotation stops, close the shut-off valve on the compressor discharge pipe;
stop the water supply;
close the line shut-off valves on the main suction manifold;
when the compressors are stopped for a long time, be sure to drain the water from the cooling jackets.
Before starting the pumps:
check the lubrication in the bearings;
check the pump rotor (manually);
open the valve on the suction gas pipeline (the valve on the discharge gas pipeline must be closed);
fill the pump with the liquid phase of the gas;

turn on the electric motor;
open the valve on the discharge gas pipeline.
When the required discharge head is reached, close the valve on the bypass line. To avoid cavitation, the pressure of the liquid phase of the gas supplied to the pump must be higher than the vapor pressure of LPG. It is forbidden to leave running compressors and pumps unattended.
Stopping the pump is carried out in the following order:
turn off the motor;
open the valve on the bypass line;
close the valves on the discharge and suction lines of the pump, as well as all the valves and valves that were open during the operation of the pump.
After the shutdown of the process equipment, each unit is subjected to an external inspection in order to identify possible malfunctions (gas leaks, loose bolts, etc.). All noticed malfunctions should be immediately eliminated and recorded in the log.
Commissioning of the gas filling station equipment (compressors, pumps, evaporators) after maintenance and repair must be carried out in accordance with the instructions for the operation of the equipment. Operation of pumps and compressors with disconnected or failed automation, alarms, as well as blocking with fans of exhaust systems is prohibited.
Draining LPG into tanks
LPG is delivered to filling stations in special tank trucks. Draining LPG from tankers of autogas carriers is a gas hazardous work and must be carried out in compliance with the "Safety Rules in the Gas Industry" and production instructions. As a rule, LPG is discharged from tankers only during daylight hours. The autogas carrier arriving at the filling station must be equipped as follows:
the exhaust pipe and muffler must be brought to its front;
the exhaust pipe must have a spark arresting grid;
the autogas carrier must have two carbon dioxide fire extinguishers OU-2.
Reception and inspection of arrived autogas carriers with LPG are carried out by a shift foreman of the filling station.
When accepting an autogas carrier with LPG, the shift foreman is obliged to check:
compliance of the tank and the amount of filled LPG with the shipping documents;
the presence of seals on the drain fittings;
no damage to the tank body and serviceability of shut-off and control valves and rubber-fabric sleeves;
the presence and level of LPG in the tank according to the control valves and level gauge.
The shipping documents must contain: the name of the supplier, the date of shipment, the number of the tank, the mass (weight) of the gas filled into the tank.
The serviceability of the shut-off valves on the tank is checked by external inspection. Valves should be opened smoothly, without causing hydraulic shocks. Preparation for unloading and unloading of LPG from a gas truck into the gas filling station tanks is carried out by cylinder fillers and repairmen under the guidance of a shift foreman. During the drain operation, at least two people of the filling station service personnel must be present.
Prior to the start of LPG draining from the gas truck tank, the service personnel of the filling station must perform the following preparatory work:
secure the autogas carrier with special wooden shoes or shoes made of non-sparking metal;
make sure that the flexible hoses for draining the LPG from the tank are in good condition and reliable;
ground the tanker.
The permission to drain the LPG from the gas truck tank is issued by a shift foreman, who also gives orders to the persons employed at the drain to perform certain operations to prepare and carry out the drain of the LPG.
Draining of LPG from the tanker of an autogas carrier into the tanks is allowed only after the shift foreman and maintenance personnel are convinced of the correct opening and closing of the valves associated with this technological operation.
Draining operations must be carried out by personnel in standard work clothes, headgear and goggles.
Draining LPG from autogas carriers at gas filling stations is carried out by one of the following methods:
creation of the necessary pressure drop between the gas truck tank and the tank by pumping the LPG vapor from the tank of another group into the tank truck by the compressor;
creation of a pressure drop between the gas truck tank and the tank by heating the LPG vapor in the evaporator;
pumping LPG pumps;
by gravity, when the tanks to be filled are located below the tank car.
It is forbidden to create a pressure difference between the gas truck tank and the tank by releasing the vapor phase of gas from the tank being filled into the atmosphere.
The pressure of the vapor phase injected by the compressor or created by the evaporator in the gas truck tank must not exceed the operating pressure indicated on the gas truck tank plate. When the pressure in the gas truck tank rises above the working one, the compressor or evaporator must be immediately turned off. The pressure drop between the gas truck tank and the tank, as a rule, is allowed 0.15-0.2 MPa (1.5-2 kgf / cm2). When draining LPG from the tanks of gas carriers, the operation of the engine of the gas carrier is prohibited. After completion of the preparatory operations for draining the LPG and checking the gas truck by the service personnel, before removing the seals from the drain fittings, the driver of the gas truck is obliged to hand over the ignition keys to the gas filling station shift foreman.
It is prohibited for the driver of an autogas carrier to be in the cab during the LPG drain.
It is allowed to remove the plugs from the drain fittings of the gas truck tank only after the engine of the gas truck is stopped, and it is allowed to turn on the engine only after disconnecting the hoses from the process gas pipelines of the gas filling station and installing plugs on the drain fittings. After draining the LPG, the vapors should be removed from the tanks of the autogas carrier to a pressure of 0.05 MPa (0.5 kgf/cm2).
Discharge of gas into the atmosphere is prohibited.
During the LPG drain, it is prohibited for service personnel who are not involved in the drain operations to be near the gas carriers.
It is forbidden to keep tankers of autogas carriers connected to the technological gas pipelines of gas filling stations when the LPG is not drained.
The personnel involved in draining are obliged to monitor the tightness of all connections of technological gas pipelines, tanks and tanks of autogas carriers. If a gas leak is detected, the emergency section is turned off and measures are taken to eliminate it. During the LPG drain, it is forbidden to carry out any work to seal the joints under pressure; it is only allowed to disconnect the flexible hoses of the gas truck only after the tank has been turned off and the pressure in the drain hoses has been relieved. It is strictly forbidden during LPG draining to leave unattended the gas carrier tank, drain gas pipelines, tanks, operating compressors, pumps and evaporators.
During the period of draining, continuous monitoring of the pressure and level of gas in the tank car and the receiving tank must be ensured.
The tanks are filled with LPG to no more than 85% of their geometric volume. In case of tank overflow, the excess gas must be drained into other tanks. The release of excess gas into the atmosphere is prohibited.
Draining operations of LPG at filling stations during a thunderstorm, as well as during hot work in the production area, are prohibited.
During the LPG drain period, visual communication should be provided between the personnel servicing process gas pipelines and equipment (drain columns, compressors, pumps and evaporators). At the end of the drain, the valves on the gas truck tank must be plugged with plugs and checked for leaks with a soapy emulsion. Rubber-fabric sleeves (hoses) of autogas tankers must be attached to the drain tip with steel clamps (at least two clamps for each end of the hose). Wire clamps are not allowed.
Draining LPG is prohibited if the sleeves (hoses) have cracks, fractures, potholes and other damage and consist of separate parts. Sleeves with external metal spirals are considered unsuitable if the spirals are broken or partially missing. To thaw frozen fittings and drain gas pipelines, heated sand, hot water, and steam should be used. The use of fire is strictly prohibited.
In the event that an autogas carrier with LPG that has a leak enters the gas filling station, the tank must be immediately unloaded according to a special instruction that provides for additional security measures. In this case, a defective act is drawn up. It is prohibited to carry out repairs of an autogas carrier on the territory of the gas filling station.
It is forbidden to fill tanks with gas in cases provided for by the Rules for the Design and Safe Operation of Pressure Vessels, as well as:
if cracks, bulges, omissions or sweating in welds are found in the main elements of the tank, leakage in flanged joints, gasket ruptures;
in case of malfunction of safety valves;
in case of malfunction of level measuring devices;
in case of malfunction or incomplete number of fasteners on manholes and hatches;
during the settlement of the foundations of tanks and supports of the supply gas pipelines.
In the room of the pump-compressor department, the technological unit or in the control unit, the following are posted in a conspicuous place:
piping scheme of technological equipment with drain, dispensing columns and reservoirs;
scheme for draining LPG from gas tankers;
production instructions for draining LPG;
safety instructions for LPG drain operations.
In the area of ​​LPG draining, warning posters should be posted with safety requirements when draining LPG from tankers of autogas carriers.
Labor safety requirements for refueling
LPG vehicles
Refueling of gas-balloon cars is carried out according to the production instructions. Responsibility for the technical serviceability of cylinders of gas-cylinder vehicles and their examination lies with the owner of the vehicle. Cylinders are subject to inspection once every two years. The suitability for filling automobile cylinders must be confirmed by a stamp in the driver's waybill (route) "Cylinders checked", certified by the signature of the person responsible for supervising the technical condition and operation of the cylinders. The procedure for refueling personal vehicles is determined by the instructions. Before refueling cylinders, the gas filling station operator is obliged to check in waybill the presence of a stamp and signature confirming the serviceability and suitability of the cylinders for filling, as well as the driver’s certificate for the right to drive a gas-balloon car. On the cylinder installed on the car, the following data should be knocked out and clearly visible:
manufacturer's trademark;
cylinder number (factory);
the actual mass of an empty cylinder (kg) in accordance with GOST or TU for their manufacture;
date (month, year) of manufacture and year of the next survey;
working pressure (P), MPa (kgf/cm2);
test hydraulic pressure (P), MPa (kgf/cm2);
cylinder capacity (l) in accordance with GOST or TU for their manufacture;
number of the standard for their manufacture.
It is forbidden to refuel LPG cylinders installed on vehicles that have:
the period of periodic examination has expired;
no installed inscriptions;
valves and valves are not fixed;
the cylinder body is damaged (shells, nicks, corrosion, dents);
the cylinder fastening is loosened;
there are leaks from various connections.
Refueling of cylinders installed on gas-balloon vehicles is carried out if the driver of the car has a registration coupon for a gas-balloon installation. The ticket must indicate:
car name;
city ​​number of the car;
serial number of the cylinder;
cylinder capacity in l;
date of the next technical examination of the cylinder;
seal and signature of the registering organization or vehicle fleet.
Filling LPG car cylinders is allowed only when the car engine is turned off. It is allowed to turn on the engine only after disconnecting the sleeves and installing a plug on the shutdown devices. Entry into the territory of the gas filling station and refueling of vehicles in which passengers are located are prohibited.
The degree of filling of the cylinder is determined by the maximum filling control valve or shut-off valve. Overfilling the balloon is not allowed.
If leaks are found in the gas equipment of the car or the cylinder is overfilled, the gas from it must be drained into a tank.
When refueling LPG vehicles, the following rules must be observed:
do not knock with metal objects on fittings and gas pipelines under pressure;
if the engine of a car filled with gas during the descent gives interruptions (pops), it should be immediately turned off and the car should be rolled away from the gas station at a distance of at least 15 m;
do not transfer the car engine from one type of fuel to another on the territory of the filling station;
not to adjust and repair the gas equipment of gas-balloon vehicles on the territory of the gas filling station;
do not create a pressure on the filling column that exceeds the working pressure of the cylinder;
do not tighten connections on cylinders and communications;
do not leave gas stations and cars unattended;
do not release LPG from cylinders into the atmosphere when overfilled.

Safety measures during survey of tanks
Tanks before internal inspection, hydraulic testing, repair or dismantling must be freed from gas, unevaporated residues and carefully processed. The release of tanks by discharging gas through a candle into the atmosphere is not allowed. The burning of the vapor phase residues should be carried out on a "candle" made of a steel pipe with a diameter of 20 mm, a height of 3 m and installed on a stable tripod in a fireproof place at a distance of 10-12 m from the border of the tank installation with an inclination of 50-60 ° to the horizon. Filling the tank with water should begin at the moment when the flame on the "candle" decreases to 20-30 cm, while the combustion of the vapor phase displaced by water should continue until the flame goes out.
The water supply must be stopped when the tank is full.
Processing of tanks should be carried out after disconnecting them from the gas pipelines of the vapor and liquid phases using plugs. Tanks should be treated by steaming and purging with an inert gas or filling with warm water. The quality of the degassing should be checked by analyzing air samples taken from the bottom of the vessel. The concentration of the LPG sample after degassing should not exceed 20% of the lower flammability limit of the gas. Depressurization of tanks without first reducing the pressure in them to atmospheric, as well as the use of air for degassing, are not allowed.
Work inside the tanks should be carried out by a team of at least three people under the supervision of a specialist in compliance with the following basic safety measures:
simultaneous descent into the tank by more than one person is prohibited;
the person working in the tank must have a hose gas mask and put on a rescue belt with a signal-rescue rope attached to it;
outside the tank there should be at least two people who should hold the ends of the ropes in their hands, observe the worker in the tank, be ready to provide him with the necessary assistance and not allow unauthorized persons to the place of work;
the residence time in the tank should not exceed 15 minutes;
the work team must be equipped with special protective equipment, special tools and explosion-proof flashlights;
every 30 minutes, check the tank for gas contamination with a portable gas analyzer. If a gas concentration above 20% of the lower flammable limit is detected, work in the tank should be stopped, people should be removed and re-degassing should be carried out, followed by a gas check.
During work in the tank, persons who are not related to these works are prohibited from being near the tank.
Sediments removed from the tanks must be kept moist and immediately removed from the territory of the gas filling station for disposal in a specially designated place. Sections of gas pipelines with pyrophoric deposits must be dismantled and stored in a safe area on the day they are opened. Water after washing and testing of tanks should be discharged into the sewerage system only through settling tanks, which exclude LPG from entering the sewerage system, or taken out to places determined by the sanitary and epidemiological supervision. The tanks must be put into operation after examination or repair on the basis of the written permission of the head of the enterprise (organization, etc.) of the gas filling station.
Measures to ensure the safety of work
during the operation of electrical installations
At the gas filling station, organizational measures must be taken to ensure the safety of work in electrical installations:
registration of work by an admission order (hereinafter - an order), an order or a list of works performed in the order of current operation;
work permit;
supervision during work;
registration of a break in work, transfers to another workplace, termination of work.
Work can be carried out along the way:
a) with stress relief;
b) without removing the voltage on current-carrying parts and near them.
By order can be made:
a) work without removing voltage away from live parts under voltage, lasting no more than one shift;
b) work caused by production necessity, lasting up to one hour;
c) work with voltage removal from electrical installations with voltage up to 1000V for a duration of not more than one shift.
The list of persons who are granted the right to issue orders and orders is determined by the order for the enterprise.
Electrical installations that are inactive for a long time (the time is determined depending on local conditions), before switching on, must be tested for compliance with the state of their insulation with electrical rules and regulations.
During electrical work in explosive areas of premises and outdoor installations, the following conditions must be met:
work must be carried out with the permission of the person who issued the order, by a team of at least two people;
technical measures have been taken to ensure the safety of work, the necessary shutdowns have been made and measures have been taken to prevent the supply of voltage to the place of work due to erroneous or spontaneous switching on of switching equipment;
prohibitory posters are hung on the manual drives and on the remote control keys of the switching equipment;
the absence of voltage on current-carrying parts, on which grounding must be applied to protect people from electric shock, was checked;
grounding is applied (grounding knives are turned on, and where they are absent, portable grounding devices are installed);
warning and prescriptive posters were hung out, workplaces and current-carrying parts remaining energized were fenced, if necessary.
It is forbidden to work with electric drills and other portable power tools and devices that produce sparks. When conducting electrical measurements directly in an explosive room, gas pipelines and equipment must be turned off. It is necessary to turn on the transformers under load first from the load side, they must be turned off in the reverse order.
Before use, protective equipment must be carefully inspected, cleaned, checked for external damage, and also for branding: whether they correspond to the voltage of this electrical installation and whether the period of periodic testing has expired.
If a malfunction or an expired test mark is detected, protective equipment must be immediately withdrawn from service.
Gas hazardous work
Gas-hazardous work, which provides for the development and subsequent implementation of a set of measures for the preparation and safe conduct of them, is issued by a work permit. These works include:
launching gas into gas pipelines and other technological equipment of gas filling stations during commissioning after completion of construction, reconstruction, expansion and overhaul, during depreservation;
commissioning;
initial filling of tanks with liquefied gas during their commissioning, as well as after repair, cleaning, technical examination;
removal of blockages, installation and removal of plugs on existing gas pipelines, as well as disconnection of units, equipment and individual units from gas pipelines;
disconnection from the existing network and purging of gas pipelines, conservation and depreservation of gas pipelines and technological equipment of gas filling stations;
preparation for technical examination of LPG tanks;
repair of existing internal and external gas pipelines, equipment of pump and compressor departments, filling stations, LPG tanks;
dismantling of gas pipelines, tanks, technological equipment of gas filling stations;
current repairs associated with the dismantling of fittings, pumps and compressors at the work site;
excavation of soil in places of gas leakage until it is eliminated;
all types of repairs related to the performance of welding and hot work on the territory of the filling station;
conducting electrical tests in hazardous areas.
Periodically recurring gas hazardous work performed under similar conditions, as a rule, by a permanent staff of performers and being an integral part of the technological process, can be carried out without issuing a work permit according to production instructions approved for each type of work.
Such works are: maintenance of stop valves, safety valves and checking their settings;
maintenance of technological equipment of gas filling stations;
repair, inspection and ventilation of wells;
repair work without the use of welding and cutting in wells, trenches, recesses;
draining LPG from tankers into tanks, pumping out unevaporated residues of liquefied gases from tanks, refueling LPG vehicles, draining gas from overfilled cylinders;
replacement of instrumentation on process equipment.
These works must be recorded in the register of gas hazardous work. The magazine must be laced and sealed, the pages in it must be numbered.
Works on launching gas into gas pipelines and technological equipment of gas filling stations, repairs using welding and gas cutting, reactivation of gas filling stations, commissioning, initial filling of LPG tanks are carried out according to a work permit and a special plan approved by the chief technical manager of gas filling stations. The work plan indicates the strict sequence of their implementation, the arrangement of people, the need for mechanisms, devices and materials, measures are provided to ensure the safety of each gas-hazardous work, indicating the persons responsible for carrying out and preparing the work. Responsibility for coordination specified works and the implementation of general management are assigned to the chief technical manager of the enterprise or a person replacing him. Works to eliminate gas leaks and liquidate accidents are carried out without work permits for gas hazardous work until the direct threat to maintenance personnel, material assets, buildings and structures is eliminated and are carried out according to the "Plans for Localization and Elimination of Accidents".
The work permit of the established form is issued to the responsible person for the performance of gas hazardous work signed by the chief engineer or head of the enterprise for each type of work for each team and is valid for one shift. If the work turned out to be unfinished, and the conditions for its implementation and nature have not changed, the work permit may be extended for the next shift of the same team by the person who issued it.
To prepare the facility for gas hazardous work, a set of preparatory measures provided for in the work permit and relevant instructions must be carried out. Before starting gas-hazardous work, the person responsible for its implementation is obliged to check the availability and serviceability of personal protective equipment, as well as to instruct the performers on the necessary safety measures when performing work, after which each person who has received the instruction signs the work permit.
The work on the side-admission must be registered in a special register of gas hazardous work, the journal must be laced and sealed, the pages in it must be numbered. Work permits must be kept for at least one year. Work permits issued for the primary discharge of gas, the performance of repair work using welding on the elements of technological gas pipelines and tanks in the ground, are permanently stored in the executive and technical documentation of the gas filling station.
The register of gas hazardous work must be kept for 5 years.
Gas hazardous work at the gas filling station must be carried out by at least two workers. Work in tanks, station premises, as well as repairs using gas cutting and welding are carried out by a team consisting of at least three workers under the guidance of specialists.
Inspection, repair, ventilation of wells, discharge of unevaporated LPG residues from tanks and cylinders, maintenance of gas pipelines and process equipment, filling of LPG tanks during operation is allowed to be carried out by two workers. The management of these works may be entrusted to the most qualified worker. Refueling of LPG vehicles can be carried out by one operator.
Female persons may be involved in certain gas-hazardous work provided for by the technological regulations and instructions and permitted by the legislation on the labor of women. When organizing a workplace for gas hazardous work, the responsible person is obliged to ensure that workers can quickly withdraw from the hazardous area. Gas-hazardous work at gas filling stations, carried out according to work permits, is carried out, as a rule, in the daytime. In exceptional cases, urgent gas-hazardous work may be permitted at night, provided that additional measures are taken to ensure the safe conduct of work.
On the territory and in the premises of gas filling stations, it is not allowed to carry out welding and cutting on existing gas pipelines without shutting them down and purging with inert gas or steam, as well as dismantling flanged threaded connections, fittings and equipment in non-disconnected and non-purged sections of the gas pipeline. When disconnecting gas pipelines and equipment, plugs must be installed at closed disconnected devices.
Pumps and compressors must be stopped for the duration of gas hazardous work in the pump and compressor room. All gas pipelines and gas equipment, before being connected to existing gas pipelines, as well as after repair, must be subjected to external inspection and control pressure testing with air or inert gases. Control pressure testing of internal gas pipelines and gas filling station equipment should be carried out with a pressure of 0.01 MPa (1000 mm of water column). The drop must not exceed 600 Pa (60 mm wg) in one hour. LPG tanks, gas pipelines must be tested with a pressure of 0.3 MPa (3 kgf/cm2) for one hour. The results of the control pressure test are considered positive in the absence of a visible drop on the pressure gauge and leaks, determined using a soap emulsion or devices.
The results of the control pressure test must be recorded in the work permits for the performance of gas hazardous work. Gas pipelines and equipment must be purged with inert gas or liquefied gas vapors before starting the gas until all air is displaced.
The fittings intended for purging the gas storage vessels should be located on them in such a way as to ensure the purging of the entire volume of the technological apparatus with minimal purge gas consumption.
When organizing purging with liquefied gas vapors, measures must be developed for its safe conduct, excluding the ignition of the gas-air mixture from any source of fire. The end of the purge is determined by analysis. The volume fraction of oxygen in the gas sample should not exceed 1%.
In the process of performing gas hazardous work, all orders on the procedure for their implementation must be given by the person responsible for the work. Others present during the work officials and managers can give instructions to workers only through the person responsible for carrying out this work.
In a place where gas hazardous work is carried out, it is forbidden for unauthorized persons to be. Emergency work at gas filling stations is carried out by the personnel of these enterprises. The participation of emergency services of gas facilities in emergency work at gas filling stations is established by an agreed plan for the localization and elimination of accidents.
The activities of engineering and technical workers and workers of gas filling stations for localization and liquidation of emergency situations should be determined by the plan for localization and liquidation of accidents and the plan for the interaction of services of various departments. The plan for localization and liquidation of the accident should take into account the specifics of the technological process and be developed in compliance with the requirements of the instructions for safe work methods. The plan should include:
methods and means for extinguishing a fire;
a list of persons (indicating telephone numbers and other means of communication and calling) who must be immediately notified of the accident;
procedure for notification of an accident;
plan for the evacuation of vehicles from the danger zone;
possible emergencies that are dangerous to human life and health, the safety of material assets, environmental protection;
distribution of responsibilities and the procedure for specific actions of the gas station personnel for the prevention and elimination of accidents and interaction between individuals involved in the liquidation of the accident;
ways to eliminate the accident and the list of necessary material and technical means;
conditions of interaction with fire protection services, police, ambulance, power supply, water supply organizations, etc.
Responsibility for drawing up the plan, the timeliness of making changes and additions to it, revision (at least once a year) lies with the chief technical manager of the gas filling station. The plan of interaction between the services of various departments for the localization and elimination of accidents at gas filling stations must be agreed with interested organizations and approved local authorities executive power.
Training sessions on localization and liquidation of accidents should be held at the gas filling station at least once a quarter.
Conducted classes should be recorded in a special journal.
hot work
Repair work associated with the use of open fire, as well as burning out the remains of the LPG vapor phase from tanks, is allowed in exceptional cases, provided that the employees comply with the "Safety Rules in the Gas Industry", "Fire Safety Rules for Welding and Other Hot Works at National Economy Facilities" , approved by the GUPO MVD, "Standard instructions for organizing the safe conduct of hot work at explosive and explosive objects", approved by the Gosgortekhnadzor of Russia, and the requirements of these Rules.
Hot work must be carried out in the daytime according to a special plan approved by the management of the gas filling station, agreed with the local fire brigade and the work permit. The work permit for conducting hot work must be issued in advance to carry out the necessary preparation for work. The permit must state:
place and time of work and their nature;
surname, name, patronymic, position of persons responsible for the preparation and conduct of hot work;
the list and sequence of preparatory measures and safety measures in the performance of hot work;
the composition of the brigade with a mark on the passage of the briefing;
the results of the analysis of the air environment before work.
The management of the preparation and conduct of hot work, as well as their implementation, can be entrusted to persons who have undergone the necessary training in accordance with the requirements of GOST 12.0.004 and the fire-technical minimum.
The person who approved the special plan and issued the work permit is responsible for the correctness and completeness of the developed measures for the preparation and conduct of hot work, as well as for the sufficient qualifications of the persons included in the work permit as managers and performers of work. Hot work is allowed to be carried out only after all the preparatory work and activities provided for by the plan and work permit have been completed. Preparatory gas hazardous work (purging, degassing, etc.) must be carried out in accordance with the requirements of the "Safety Rules in the Gas Industry". During the period of preparation for hot work, measures should be taken to turn off the equipment, install plugs, degas the repaired equipment and gas pipelines, etc., excluding the possibility of gas penetration to the work site. Preparation of technological equipment for repair (shutdown, degassing), dismantling and installation after repair, as a rule, is allowed to be performed during daylight hours. It is allowed to disassemble threaded and flange connections of fittings and equipment only after the installation of a shunt jumper and their release from gas. Bleed gas from the gas pipeline section to be repaired only through purge candles. It is not allowed to bleed gas through the gap of separated flange connections. When venting gas, all mechanisms must be outside the security zone on the windward side.
The place of hot work should be provided with fire extinguishing equipment (fire extinguisher, sandbox, shovels, bucket of water, felt mat, etc.). A fire hose with a barrel from the internal fire water supply should be laid to the place of work. To protect equipment, combustible structures from sparks of an electric arc, welders' workplaces must be fenced with portable metal shields, equipment and combustible structures - with metal sheets or asbestos blankets. When carrying out hot work at a gas filling station, it is prohibited to carry out operations for receiving LPG and refueling vehicles, while road signs must be installed prohibiting the entry of vehicles into the territory of the gas filling station.
The person responsible for conducting hot work is obliged to instruct the performers on fire safety measures during their conduct, to determine fire prevention measures for preparing the work site in accordance with fire safety requirements. It is possible to start carrying out hot work only after all the preparatory measures specified in the work permit have been completed and if the fire extinguishing equipment provided for by the work order is available at the work site.
The implementation of preparatory measures that ensure safe working conditions must be checked before they begin by the person responsible for its implementation. During the period of work responsible person control over compliance with fire safety and safety requirements should be established.
When performing work inside the premises, posts should be set up outside in order to prevent unauthorized persons from accessing the place of work. During the entire time of work in the premises, supply and exhaust ventilation must operate.
When repairing equipment and gas pipelines in which pyrophoric deposits are possible, measures should be taken to prevent their ignition.
Before starting and during hot work in the premises, as well as in a 20-meter zone from the workplace on the territory, an analysis of the air environment for the content of LPG should be carried out at least every 10 minutes. In the presence of LPG vapors in the air, regardless of their concentration, hot work should
etc.................